S7Siemens S7
Industrial CoreS7-300/400 • S7-1200 • S7-1500 • S7-200 SMART
Built Pure-JS ISO-on-TCP engine in the server process. The PDU size is negotiated from the PLC (240, 480 or 960) and reads are coalesced within a 64-byte gap. The CPU family is a required connect property — there is no auto-detection — and unsupported types are refused with an actionable error rather than a silent fallback.
- Wire transport
- TCP port 102 (ISO-on-TCP)
- Address syntax
- DB1.DBX0.0 / DB10.DBD4 (REAL) / MW10
Device types: SiemensS7Direct socket • In-process
OPC-UAOPC UA
Industrial CoreSouthbound client & northbound server
Built Southbound: address-space browsing, monitored-item subscriptions with deadband filtering. Northbound: a server under the urn:cirio:scada namespace, defaulting to the Basic256Sha256 security policy with X.509 application certificates. Secure southbound authentication is unverified against a vendor server.
- Wire transport
- opc.tcp (port 4840)
- Address syntax
- ns=2;s=Line1.Boiler.Temp
Device types: OPCUADirect socket • In-process
MODBUSModbus
Industrial CoreTCP • RTU • Schneider & Delta memory maps
Built One driver serves multiple device types: ModbusRTU, ModbusTCP, Schneider and Delta. Function codes 01–06, 15 and 16, with configurable byte and word order for Word, DWord and Float. Schneider (M221, M241, M340, M580) and Delta (DVP, AS, AH) are memory-map profiles inside this driver — they are address conventions, not separate drivers.
- Wire transport
- TCP port 502 / serial RS-485
- Address syntax
- Holding reg 40001 / %MW100 / D100
Device types: ModbusRTU · ModbusTCP · Schneider · DeltaDirect socket • In-process
BACNETBACnet
Industrial CoreBuilding automation · object supervision
Built Addressed by device instance plus a type-instance object id, with the object type bounded at 1023. Read Property Requests are grouped per device and capped at 24 objects per request; writes go through the writable-value encoding for the object type.
- Wire transport
- UDP port 47808 (0xBAC0)
- Address syntax
- device 12, object 0-1 (analog value 1)
Device types: BACnetDirect socket • In-process
MQTTMQTT client
Industrial CoreBroker subscribe & tag publish
Built A southbound client: subscribes to broker topics and maps payloads onto tags, and publishes a tag back on write. MQTT 3.1.1 and 5.0 are both implemented. Certificate verification can be switched off per device, and the driver logs a warning when it is.
- Wire transport
- TCP 1883 / TLS 8883 / WebSocket
- Address syntax
- factory/line2/press/telemetry
Device types: MQTTclientDirect socket • In-process
EIPEtherNet/IP
Industrial CoreExplicit messaging · PCCC scalars
Built Explicit TCP messaging carrying PCCC Execute PCCC, service code 0x4B in the ODVA CIP service-code table. The supported contract is PCCC scalar reads and scalar writes against data-table files — native symbolic tag names, UDP implicit I/O, discovery and arrays are out of scope, and addresses in those forms are refused rather than guessed.
- Wire transport
- TCP port 44818
- Address syntax
- N7:0 (INT) / F8:0 (REAL) / B3:1/1 (BIT)
Device types: EthernetIPDirect socket • In-process
MELSECMitsubishi MELSEC
Industrial CoreiQ-R • iQ-F • Q series
Built SLMP over Ethernet. Buffer-memory limits are derived per series from MC-REF and SLMP-RM rather than one flat cap: iQ-F and QnA cap a BUFFER request at 960 word points, and iQ-R refuses a buffer-memory base outright because it needs the device extension specification.
- Wire transport
- TCP/UDP 1025 & 5007
- Address syntax
- D1000 / W10A / X020 / M100
Device types: MELSECDirect socket • In-process